FIRE FIGHTING

22 Jan 2016

By KHEOH YONG SHEN

 

Notes on Fire Fighting Requirements

Fire Lift

UBBL
GFPM pg242

- To provide: If top occupied floor is over 18.5m from fire appliance access level.

- Location:

   - Not more than 61m travel distance from further point of floor & main entrance of the building/ fire control room.

   - Within a separate protected shaft and opens into a separate protected lobby containing the rising mains.​

[WEBSITE UNDER MAINTENANCE]

___________________________________________________________________________________________________________

Reference:

 

1. UBBL 1984

2. Prof. Datuk Dr. Soh Chai Hock (1999). Guide to Fire Protection in Malaysia.

3. http://www.slideshare.net/zhaoweiKim/passive-fire-protection-according-to-ubbl-malaysia